IRON CONTROL PANEL

Central convencional Cofem

Automatic conventional fire detection and fire alarm control panel.

This fire control panel provides different versions to fit more accurately to the needs of each facility:

  • IRON02: IRON control panel with 2 detection zones.
  • IRON04: IRON control panel with 4 detection zones.
Features
  • 2 or 4 zones control panels for use with conventional detectors and alarm call points.
  • Up to 32 elements (with detectors and alarm call points) per zone.
  • 2 supervised general sounder outputs, delayable from 0 to 7 minutes, each protected by a self-rearming fuse.
  • 1 immediate alarm output using a NO/NC (Normally Open/Normally Closed) dry contact.
  • 1 immediate fault output using a NO/NC (Normally Open/Normally Closed) dry contact.
  • 1 auxiliary 30 V/DC output supervised and protected by a self-rearmable fuse for external power supply (fire door electromagnets, sirens, etc).
  • It has a Test Mode to facilitate quick and easy testing of detectors and alarm call points.
  • Allows open line, detector alarm and call points alarm thresholds to be configured to suit operation with other detectors.
  • Metal box with front screwed door, 10 pre-drilled 28 mm holes for wiring, and space for 2 x 2 Ah batteries.
  • Certified according to EN 54-2 and EN 54-4 with CE marking.
Manuals

Login to private area to check the product documentation.
Login to private area to check the product documentation.

Menu