Central de CO ZCO

Central CO sensor ZCO

CO SCO sensor, designed according to the European standard EN 50545-1 and certified UNE 23300.

The sensor is designed to work with all models of COsensor plants, both conventional (CCO and MiniCO models) and addressable (ZafirCO). In this sense, the sensor, when the control panel is turned on, recognizes the model and adapts its communication to the one required by it.

The detector sensor is based on electrochemical technology that allows it to respond appropriately to CO concentrations in the environment and send this information to the control panel. In this way, the control panel will act appropriately by activating the necessary ventilations and alarms.

The sensor also contains a red LED that in normal operation flashes every 10 seconds approximately. Connected to conventional power plants, the flashing is double to indicate that a concentration of 50 ppm of CO has been reached, and remains fixed when the concentration reaches 200 ppm of carbon monoxide (CO). Connected to addressable control panels, the flashing is double when the concentration read by the sensor is equal to or higher than the ventilation level programmed in the zone, and fixed when the reading is equal to or higher than the alarm level also programmed in the zone.

CO sensors should be distributed throughout the enclosure in accordance with installation standards/regulations. A recommended coverage for these devices can be between 200 and 300 m2, placing them at a height of between 1.5 and 2 m from the ground.

In addressable control panels with activated maintenance mode, the operation of the sensors can be easily checked.

Automatic COsensor addressable central station with carbon monoxide (CO) and nitrogen dioxide (NO2) diffusion sensors designed according to the European standard EN 50545-1 and certified UNE 23300.

This plant includes the ZafirCO2 (Ref. ZCO2), ZafirCO3 (Ref. ZCO3) and ZafirCO4 (Ref. ZCO4) models. Equivalent to 2, 3 or 4 zone plants with a capacity of up to 25 CO and/or 25 NO2 sensors per zone.

These models support DVB version (Double Ventilation and Batteries).

The COsensor ZafirCO central controller allows setting the activation concentration for ventilation level 1, 2 and alarm, as well as the activation delay and stop delay times for these levels/alarm.

It has independent dry contact outputs per zone for each ventilation and alarm level, as well as a general fault output and 30 Vdc auxiliary power supply.

The control panel has a maintenance mode that allows you to easily check the operation of the sensors by observing how their LED flashes when confronted with the test gas.

The control panel allows to identify, through the menu, all the sensors of the installation by means of their programming number. When this identification is not necessary, the autoconfiguration function of the control panel will automatically detect all the sensors in the zones and show them on the display. By confirming this information, the control panel enters directly into working mode.

The philosophy and mode of operation of the equipment is designed according to EN 50545-1, using diffusion sensors and factory calibration to operate throughout its operating life, and certified UNE 23300.

The test gas is then applied to the test gas and the LED flashes.

The philosophy and mode of operation of the equipment is based on a design according to EN 50545-1, using diffusion sensors with factory calibration to operate during its entire operating life, and certified UNE 23300.

Key features

  • Central units with up to 4 ventilation zones with COsensor model SCO (CO sensor) and SDN (NO2 sensor) diffusion sensors.
  • Dry contact output (COM/NA) for ventilation 1, ventilation 2 (DVB models only) and alarm.
  • Dry contact fault output (COM/NA/NC).
  • Auxiliary power supply output of 30 Vdc 1A.
  • Averaged concentration readings according to EN 50545-1 up to 60 minutes.
  • Ventilation level 1, ventilation level 2 (DVB models only) and alarm level selectable between 5 and 300 ppm CO and between 0.1 and 30 ppm NO2.
  • Delay time to start and delay time to stop ventilation 1 and ventilation 2 (DVB models only), independent and selectable between 0 and 10 minutes.
  • Activation delay time and alarm stop delay time selectable between 0 and 5 minutes.
  • Maintenance mode to check the operation of the sensors.
  • Space for 2×12 Vdc 7 Ah batteries (DVB models only).
  • Backlit LCD display with 4 lines and 40 characters.
  • Dimensions: 418 x 324 x 150 mm.
  • System designed according to European standard EN 50545-1.
  • UNE 23300 certified system.