Fire detection and alarm algorithmic control panel certified EN 54-2 and EN 54-4 in accordance with the Construction Products Directive.

The LYON REMOTE / ZAFIR / COMPACT Lyon central controller allows connecting up to 15 repeaters, by means of a 4-wire 1.5 mm2 connection (two power supply wires and two communication wires for the RS485 line). The two wires of the RS485 line will be connected from the control panel to the corresponding repeaters. The connection of the repeaters is made as shown in the attached figure.

Up to 3 repeaters can be connected to the 30V output of the Lyon Remote control panel power supply. For the C-Lyon and Zafir control panels, 1 repeater can be powered. The rest of the repeaters must be powered from the 30V output of an external power supply.

The connection of the repeaters, both communication cables and 30 V power supply cables, will be made with 2 x 1.5 mm2 twisted and shielded halogen-free cable, up to a maximum cable length of 1200 meters.

At the end of the installation, a 120 Ω resistor must be connected to the back panel of the last repeater connected.

Key features

  • Compatible with the EN 54-2 and EN 54-4 certified Lyon Remote, Zafir and Compact Lyon algorithmic control panels.

  • Connection of up to 15 ZYR Repeaters on RS-485 bus

  • 4-wire 1.5 mm² bus: 2 for data and 2 for power supply at 30 V dc

  • Halogen-free, shielded, stranded cable with a maximum length of 1,200 m

  • Power supply 30 V dc; power consumption during surveillance 150 mA

  • Lyon Remote’s 30 V output powers 3 repeaters; C-Lyon and Zafir power 1; additional repeaters require external 30 V dc source

  • Temperature range -10 °C … +50 °C and humidity 20 % … 95 % RH

  • IP30 protection

  • Dimensions 283 × 240 × 35 mm; weight 2.4 kg

  • Termination of the branch with 120 Ω resistor at the last repeater.

  • Installation and wiring according to the supplied diagram

Technical Data Sheets

Central ZAFIR

Central Zafir, algorithmic power in a compact format

Cofem’s new Zafir fire detection and alarm control panel redefines intelligent security efficiency. Certified to EN 54-2 and EN 54-4 in accordance with the Construction Products Directive, it integrates all the power of an algorithmic-addressable system in a surprisingly compact format.

Capable of managing up to 452 devices distributed in 2 loops, the Zafir concentrates intelligence and functionality in a design that optimizes space without sacrificing the performance of an advanced system.

Its full compatibility with the Lyon ecosystem ensures seamless integration into existing or new installations. Each loop component – detectors, pushbuttons, relay modules, master units and technical signal modules – self-identifies when connected, eliminating the need for manual coding or pre-configuration. This translates into a faster, more intuitive installation that is ready to grow or adapt to new requirements with minimal intervention.

The Zafir control panel not only simplifies the installation: it makes it smarter. Designed for environments where space is at a premium but safety is non-negotiable, it combines algorithmic precision, operational flexibility and a hassle-free installation experience.

Key features

  • Central base of 1 or 2 loops.
  • It allows to connect 226 points per loop.
  • All loop points are supervised, except for the KABY loop isolator.
  • Capacity for 32 relays per loop and 64 in total.
  • Allows the programming of 99 zones.
  • History that stores up to 6601 events with date and time.
  • Relay configuration with activation of 1, 2 or 3 alarm detectors.
  • Relay trip auto-configuration function.
  • Allows to configure visual and/or sound devices of the detector bases as relays fed from the loop.
  • Programmable delayed siren output from 0 to 10 minutes supervised, identified as S1.
  • Alarm output as unsupervised voltage-free relay, identified as ALARM.
  • Fault output, delayed and supervised, identified as FAULT.
  • Allows the connection of addressable sirens in the loop.
  • Evacuation button.
  • Backlit LCD display with 4 lines and 40 characters.
  • It incorporates several languages by default (Spanish, English, French, Portuguese, etc).
  • Configurable and manageable via PC software, I-Link.
  • Access to the panel keypad by means of a numeric code.
  • Allows the connection of up to 15 repeaters and/or 15 central stations in a network.
  • Cofem Remote on demand.
  • Dimensions: Black box of 363 x 331 x 96 mm.
  • Certified according to EN-54-2 and EN 54-4 and CE mark according to the European Regulation of Construction Products (UE) N° 2024/3110.

Technical Data Sheets

Central COMPACT LYON

Central Compact Lyon, modular intelligence for medium-sized installations.

Cofem’s Compact Lyon algorithmic-directional control panel is certified under the EN 54-2 and EN 54-4 standards, complying with the latest fire safety directives.

Designed with the same functional architecture as Lyon Remote, this control panel maintains full compatibility with all its elements: from wiring and analog detectors to pushbuttons, modules and sirens. This ensures frictionless integration in new installations or technological upgrades.

Compact Lyon is the ideal solution for medium-sized spaces that have traditionally opted for conventional systems. Its leap to an algorithmic-addressable platform offers all the advantages of an intelligent system: detection accuracy, advanced customization and increased operational reliability. In addition, its network capability makes it a dynamic node within scalable installations.

Thanks to its inter-plant connection functionality, it can share information and operate collaboratively, behaving as an intelligent repeater that extends the control and security of the overall system. Compact Lyon is not only versatile, it is also scalable: technology designed to grow with the needs of the environment, without compromising quality, response or protection.

Key features

  • 1- or 2-loop central station.
  • Allows 99 points to be connected per loop.
  • All points of the loop are monitored, except the KABY loop isolator.
  • Capacity of up to 16 relays per loop, 32 in total.
  • Allows the programming of 99 zones per control panel.
  • Allows relay tripping with 1, 2 or 3 elements in alarm.
  • History that stores up to 6601 events with date and time.
  • Relay configuration with activation of 1, 2 or 3 alarm detectors.
  • Relay trip auto-configuration function.
  • Allows to configure visual and/or sound devices of the detector bases as relays fed from the loop.
  • Programmable delayed siren output from 0 to 10 minutes supervised, identified as S1.
  • Alarm output as unsupervised voltage-free relay, identified as ALARM.
  • Fault output, delayed and supervised, identified as FAULT.
  • Allows the connection of addressable sirens in the loop.
  • Evacuation button.
  • Backlit LCD display with 4 lines and 40 characters.
  • It incorporates several languages by default (Spanish, English, French, Portuguese, etc).
  • Configurable and manageable via PC software, I-Link.
  • Access to the panel keypad by means of a numeric code.
  • Allows the connection of up to 15 repeaters and/or 15 central stations in a network.
  • Cofem Remote on demand.
  • Dimensions: 363 x 331 x 96 mm.
  • Certified according to EN 54-2 and EN 54-4 and EN 54-4 and CE mark according to the European Regulation of Construction Products (UE) N° 2024/3110.

Technical Data Sheets

Central LYON REMOTE

Central Lyon Remote, the intelligence that expands protection.

Cofem’ s algorithmic-addressable detection system acts like an intelligent nerve center: it recognizes in real time the exact device – sensor or pushbutton – that generates an alarm or warns of a fault, and allows all monitoring parameters – alarm levels, sensitivity, delays – to be adjusted with surgical precision. Its adaptive logic calibrates each detection point according to environmental conditions and the degree of head soiling, maintaining reliability even in harsh environments.

All loop elements – detectors, pushbuttons, relay modules, master units and technical signal modules – are self-identifying. Simply connect them: the control panel detects and numbers them without the need for dip-switches or manual programming. The result is a faster, cleaner installation that is ready to grow or reconfigure as easily as plugging in a new device.

Overall, the Lyon Remote architecture ensures proactive and evolutionary protection: technology that not only watches, but learns and adapts to guard what matters most.

Key features

  • Base station configurable up to 8 loops (226 points per loop).
  • Expandable up to 20 loops, adapting an additional box.
  • All loop points are supervised, except for the KABY loop isolator.
  • Capacity of up to 199 configurable relays per control panel.
  • Allows the programming of 99 zones per control panel.
  • History that stores up to 3308 events with date and time.
  • Relay configuration with activation of 1, 2 or 3 alarm detectors.
  • Relay trip auto-configuration function.
  • Allows to configure visual and/or sound devices of the detector bases as relays fed from the loop.
  • Programmable delayed siren output from 0 to 10 minutes supervised identified as S1.
  • Alarm output as unsupervised voltage-free relay, identified as S2.
  • Delayable fault output, identified as S3.
  • Allows the connection of addressable sirens in the loop.
  • Evacuation button.
  • Backlit LCD display with 4 lines and 40 characters.
  • It incorporates several languages by default (Spanish, English, French, Portuguese, etc).
  • Configurable and manageable via PC software, I-Link.
  • Access to the panel keypad by means of a numeric code.
  • Allows the connection of up to 15 repeaters and/or 15 central stations in a network.
  • MODBUS on demand.
  • Cofem Remote.
  • Dimensions: 424 x 330 x 160 mm (with cover).
  • Certified according to EN-54-2 and EN 54-4 and CE mark according to the European Regulation of Construction Products (UE) N° 2024/3110.

Technical Data Sheets

Relay and technical signal module MYOA-MYOAF

Relay and technical signal module MYOA-MYOAF

Microprocessed and addressable module (with short-circuit isolator) to be installed as a loop element.

Key features

This module has a relay with external 30V power supply and a technical signal input to discern the open or closed state of a dry contact. The module is protected by a 0.9A self-rearming fuse and the relay output is protected by 0.5A.

The module is powered by the loop connection, but requires a 30V auxiliary power supply to provide the necessary power to the devices governed by the relay marked “R1”. The relay is programmed with a single function (siren, maneuvers or crossed relay) as well as in its timing and combination of sensors that activate them. Likewise, the presence of voltage on the 30V auxiliary power supply line and also on the relay output is monitored. The voltage supplied by the relay output is 30V.

The technical signal input has a 10kΩ resistor connected in series with the dry contact. The contact must be open in the idle state and closed in the event of a fault. At the input (marked as IN2) it detects the closed contact with ALARM category.

There is also the MYOAF version, whose operation is identical to the MYOA, except that the closed contact is detected as a FAULT.

The MYOA monitors each external line (relay output and technical signal input) with a 33kΩ resistor on each, indicating open line or crossed line status.

The blinking of the transparent red LED indicates communication with the control panel. The permanent lighting of the red LED indicates the alarm status at its input, while the lighting of the green LED indicates the tripping of the relay.

The device is supplied in a rectangular, heat-resistant ABS box, to be mounted on surface or on DIN rail.

The module is certified according to EN 54-18 Standard, and CE mark according to the European Regulation of Construction Products (UE) N° 2024/3110.