Socket for conventional C50 detectors with EN 54-23 certified base with visual alarm and EN 54-3 sound.

There are 2 models available:

C50ZSL: D50 socket with sound and light base, addressable.
C50ZSD: D50 socket with sound base, addressable.

Typical uses for the C50ZSL and C50ZSD are spaces or rooms that require an integrated fire detector with siren and visual alarm such as hotel rooms.

The coverage of the set should not exceed the coverage of the fire detector with which it is installed, unless justified by the reason or use.

Key features tt

Technical Data Sheets

PUCAR fire alarm pushbutton

PUCAR fire alarm pushbutton

Resettable fire alarm button for conventional fire detection system.

It incorporates an action indicator (red led) that lights up in case of manual activation (alarm).

Key features

  • Easily resettable pushbutton by actuating the yellow switch on the front face.
  • Transparent protective cover on the actuating face to prevent accidental touching.
  • Immediate visual acknowledgement of the alarm status by permanent activation of the LED and triggering of a yellow tab at the bottom of the actuating face.
  • Certified by AENOR according to EN 54-11 and CE marked according to the European Construction Products Regulation (EU) Nº305/2011.

Technical Data Sheets

Indicador de acción remoto PIAL

PIAL remote action indicator

Indicador de acción remoto PIAL

PIAL remote action indicator: instant visibility where it’s needed most.

Cofem’s PIAL remote action indicator is the perfect solution for fire detection systems where visibility of the detector is limited or non-existent. Designed to clearly replicate the alarm signal, its steady red light activates when one of the system’s detectors triggers an alarm, providing an unmistakable signal that is visible from a distance.

It is ideal for use in spaces such as false ceilings, hard-to-reach areas or hotel rooms, where it makes it easy to quickly identify the location of an alarm without having to walk long distances or visually inspect each detector. Installing it on door frames or nearby walls makes it an effective tool for a swift and safe response.

Easy to install and adapt to standard mechanism boxes, the PIAL combines functionality with simplicity: technology that enhances the system’s visibility without complicating installation.

Key features

  • Alarm status can be identified in any perpendicular direction at its installation.
  • Easy connection, with polarity.
  • Can be adapted to the conduit boxes and switchgear.
  • The red light is produced by two LEDs, increasing reliability against failure of any of them.
  • Manufactured in heat-resistant ABS. Base and lid are white, red viewer.

Technical Data Sheets

Conventional power plant CLVR

Conventional power plant CLVR

Conventional automatic fire detection and alarm system.

This fire control panel includes different models in order to adapt in the most precise way to the needs of each installation:

  • CLVR 08Z: CLVR 08 Zones Central Station
  • CLVR 12Z: 12-Zone CLVR Control Panel

The characteristics of the CLVR fire fighting stations are common to all models.

Key features

  • Fire control panels up to 12 zones for use with conventional detectors and push buttons.
  • 2 supervised general siren outputs, delayable from 0 to 10 minutes, each protected by a self-rearming fuse.
  • 1 immediate alarm output through a NO/NC (Normally Open/Normally Closed) dry contact.
  • 1 immediate fault output through a NO/NC (Normally Open/Normally Closed) dry contact.
  • 2 auxiliary 30 V/DC outputs supervised and protected by a self-rearming fuse for external power supply (fire door electromagnets, sirens, etc.).
  • It has a Test Mode to facilitate quick and easy testing of detectors and pushbuttons.
  • Allows setting of open line, detector alarm and pushbutton alarm thresholds to suit operation with other detectors.
  • Supports configuring the last detection zone as a supervisory input from an external fire protection system giving fault indication.
  • Metal box with front screwed door, 4 pre-drilled holes of 28 mm and 1 rectangular hole in the bottom of 140 x 40 mm for wiring, plus space for 2 batteries of 7 Ah.
  • MODBUS protocol with RS485 output on request.
  • Possibility of ON-LINE software on PC using MODBUS functionality
  • CONTACTID on demand.
  • Certified according to EN 54-2 and EN 54-4 with CE marking.

Technical Data Sheets

Iron conventional power plant

Iron conventional power plant

Conventional automatic fire detection and alarm system.

This plant contemplates different models to adapt in the most precise way to the needs of each installation:

  • IRON02: IRON control panel with 2 detection zones
  • IRON04: IRON control panel with 4 detection zones

Key features

  • 2 or 4 zone control panels for use with conventional detectors and pushbuttons.
  • Up to 32 elements (with detectors and push buttons) per zone.
  • 2 supervised general siren outputs, delayable from 0 to 7 minutes, and each protected by a self-rearming fuse.
  • 1 immediate alarm output through a NO/NC (Normally Open/Normally Closed) dry contact.
  • 1 immediate fault output through a NO/NC (Normally Open/Normally Closed) dry contact.
  • 1 auxiliary 30 V/DC output supervised and protected by a self-rearming fuse for external power supply (fire door electromagnets, sirens, etc.).
  • It has a Test Mode to facilitate quick and easy testing of detectors and pushbuttons.
  • Allows setting of open line, detector alarm and pushbutton alarm thresholds to suit operation with other detectors.
  • Metal box with front screwed door, 10 pre-drilled 28 mm holes for wiring, plus space for 2 x 2 Ah batteries.
  • Certified according to EN 54-2 and EN 54-4 with CE marking.