Optical-acoustic alarm siren SIR24C

Optical-acoustic alarm siren SIR24C
Series of indoor and outdoor sirens to be connected directly to the siren output of the control panels or relay modules.
- Indoor/outdoor siren made of red ABS.
- High sound volume with low power consumption, EN54-3 certified.
- 32 selectable tones. Volume control.
- Automatic synchronization.
- SIR24C: Siren with light, EN54-23 certified.
- All sirens have built-in diode
Key features
- Voltage range: 9-28 Vdc
- Consumption: (using tone7) 49mA (SIR24C)
- Output volume: 107dB (tone 23)
- Operating Temperature: -25ºC to +70ºC
- Dimensions: Ø100 x 98 mm (SIR24C)
- IP protection: IP21C-SIR24C (low base) / IP65-SIR24C (high base)
Technical Data Sheets
Manuals
Optical-acoustic alarm siren SIR24F

Optical-acoustic alarm siren SIR24F
Optical-acoustic indoor alarm siren.
- Material: P.V.C. red
- Operating voltage: 30 Vdc
- Consumption at 30 Vdc: 70 mA
- Power 85 dB
- Operating temperature 5ºC to 40ºC
- Dimensions 80 x 80 x 30 mm
- Flashing flash: Yes
Key features
Technical Data Sheets
Manuals
Acoustic alarm siren SIR24P

Acoustic alarm siren SIR24P
Indoor acoustic alarm siren.
Indoor siren to be connected directly to the output of the control panels or relay modules.
Key features
- Material: P.V.C. red
- Operating voltage: 30 Vdc
- Consumption at 30 Vdc: 70 mA
- Power: 85 dB
- Operating temperature: 5ºC to 40ºC
- Dimensions: 80 x 80 x 30 mm
Technical Data Sheets
Manuals
Voice alarm device SIR24SC - SIR24SLC

Voice alarm device SIR24SC - SIR24SLC
Voice alarm device:
- Device that activates a voice message interspersed with a fire alarm sound.
- The message is selectable from its internal list. They have a built-in diode.
Key features
SIR24SC and SIR24SC+SIR24SLC:
- Voltage: 18 ÷ 28 Vdc.
- Consumption: 4 ÷ 8 mA.
- Sound: 90/100 dB selectable.
- Several selectable alarm tones.
- Temperature: -10ºC to 55ºC.
- Protection: IP21C.
- Color: red.
- Dimensions: 106 x 106 x 91mm.
- EN 54-3 certified.
SIR24SC + SIR24SLC:
Voice alarm set with luminous warning device in the base:
- EN 54-3 and EN 54-23 certified.
- W 2,4 – 7,5.
- Consumption: 18 ÷ 28 mA.
- 1 Hz (0.5 Hz selectable)
Technical Data Sheets
Manuals
Siren with light base SIR24B+BSLC

Siren with light base SIR24B+BSLC
Indoor and outdoor siren to be connected directly to the siren output of the control panels or relay modules.
- Indoor and outdoor siren made of red ABS.
- High sound volume with low power consumption, EN54-3 certified.
- 32 selectable tones. Volume control.
- Automatic synchronization.
- SIR24B: Siren.
- SIR24BL: Siren with light.
- SIR24BZA: Siren with high base.
- BSLC: Base with light, EN54-23 certified.
Key features
- Voltage range: 9-28 Vdc
- Consumption (using tone 3) at 24 Vdc 15 mA.
- Output volume (tone 3) at 24 Vdc 102 dB (A).
- Operating temperature: -25ºC to +70ºC.
- Dimensions: Ø95 x 91 mm (SIR24B), Ø95 x 135 mm (SIR24BL/SIR24BZA), Ø95 x 95 x 135 mm (SIR24B+BSLC).
- IP protection: IP54-SIR24B, IP65-SIR24BL, IP65-SIR24BZA, IP65-SIR24B+BSLC.
Technical Data Sheets
Manuals
Illuminated warning device SIRCEI - SIRWAL - SIR-PIT

Illuminated warning device SIRCEI - SIRWAL - SIR-PIT
Devices that emit flashes of light when activated to warn hearing impaired people.
Key features
SIRWAL and SIRCEI:
- EN54-23 certified.
- Power supply: 9 ÷ 60 Vdc.
- Operating temperature: -25°C to 70°C.
- High base.
- IP65 protection.
- Red color.
- Dimensions: Ø93 mm x 65 mm.
- Flash: White 1Hz (0.5 Hz selectable).
- Consumption: 10-25 mA according to selection.
A1. SIRWAL:
- Wall-mounted device.
- W 2,4 – 7,5.
A2. SIRCEI:
- Ceiling device.
- C 3 – 7,5.
SIR-PIT:
- Power supply: 9 – 60 Vdc.
- Consumption: 3 ÷ 15 mA according to selection.
- Flash: 1 flash 1Hz.
- 2 flashes 1Hz.
- Continuous 1Hz.
- Temperature: -20°C to 55°C.
- Protection: IP21C.
- Color: red.
- Red flash.
Technical Data Sheets
Manuals
Temperature probe STF - STPR

Temperature probe STF - STPR
Point heat detector based on a probe that allows installation in special environments.
Key features
Depending on the protection needs, the detector can be used in:
- Aggressive environments: IP65 models.
- ATEX environments: II2GD Exd IIC T6.
Technical Data Sheets
Manuals
Alarm bell CA6

Alarm bell CA6
6-inch interior alarm bell.
Features
- 6″ interior alarm bell.
- Operating voltage 24 Vdc
- Consumption: 25 mA
- Output volume: 95dBA at 1 meter, 92dBA at 1 meter (EN 54-3)
- Operating temperature: -20ºC to 60ºC
- Max. humidity: 90% RH
- Dimensions: 6″ (150 mm x 56 mm)
- Weight: 850 g
- Protection: IP21
Key features
Technical Data Sheets
Manuals
MDL1R - MDL2R - MDL-8 Relay Modules

MDL1R - MDL2R - MDL-8 Relay Modules
Relay module for fire detection system. This module consists of a relay that controls the output of a dry contact Normally Open (NO) Normally Closed (NC), unsupervised.
This arrangement allows to control as a typical application the triggering of door electromagnets and fire dampers in conventional fire detection systems, either through the power supply of the control panel or through External Power Supplies (EPS).
The equipment is very simple and easy to install.
The relay module circuit is mounted on a plastic base, which has adhesive tapes that allow it to be conveniently fixed in the most convenient place, taking advantage of the space available in the control panels, Power Supplies (FAE), etc., following the normal distribution of the installation wiring.
In addition, the relay module contains a safety fuse on the dry contact side.
Three versions of modules are available depending on the number of relays contained on the base:
- MDL1R: Module consisting of 1 relay.
- MDL2R: Module consisting of 2 relays.
- CDM-8: Module consisting of 8 relays.
Key features
- Relay with dry contact output NO-NC, unsupervised.
- Easy installation by means of adhesive tapes, taking advantage of the useful space and following the normal wiring distribution.
- Contains safety fuse.
Technical Data Sheets
Manuals
A30XBI adapter socket

A30XBI adapter socket
To facilitate the task of upgrading the TC25/A system to the Lyon system (and in general, the conventional system), Cofem has an “interconnection base”, which allows the detectors of the analog and conventional system to be placed directly on the sockets of superior systems without the need to change or rewire the sockets.
In this way, if the wiring and sockets of the installation are in good condition, a quick, simple and very economical upgrade of the system can be carried out, based on the replacement of the fire detection and alarm control panel and its detectors.
The A30XBI adapter can be used with conventional and analog detectors, and are supplied configured in relation to the detectors to be replaced.